How it works
The efficiency and reserve are user assumptions. Energy is a first-order estimate; real UPS runtime depends on discharge rate, battery age, temperature and the manufacturer’s runtime curve. Check both watt and VA ratings and startup surges; this does not select a UPS model.
Worked example
A 600 W load with a power factor of 0.8 and a 20% capacity reserve gives a UPS sizing scenario of 900 VA and 720 W, and 15 minutes of runtime at 90% battery-to-load efficiency takes 166.7 Wh of battery energy.
How the apparent capacity scenario changes with load
Other inputs keep their starting values: Load power factor: 0.8; Runtime wanted (minutes): 15; Battery-to-load efficiency (%): 90; Capacity reserve (%): 20. Examples only, not recommendations.
| Load (watts) | Apparent capacity scenario (VA) |
|---|---|
| 300 | 450 |
| 600 | 900 |
| 1,200 | 1,800 |