Updated
Using UPS sizing calculator
VA rating scenario = watts ÷ power factor × reserve factor. Battery energy = watts × runtime hours ÷ efficiency.
The efficiency and reserve are user assumptions. Energy is a first-order estimate; real UPS runtime depends on discharge rate, battery age, temperature and the manufacturer’s runtime curve. Check both watt and VA ratings and startup surges; this does not select a UPS model.
A worked example
For load (watts) = 600, load power factor = 0.8, runtime wanted (minutes) = 15, battery-to-load efficiency (%) = 90, capacity reserve (%) = 20, apparent capacity scenario (va) = 900.
Before you use the result
The efficiency and reserve are user assumptions. Energy is a first-order estimate; real UPS runtime depends on discharge rate, battery age, temperature and the manufacturer’s runtime curve. Check both watt and VA ratings and startup surges; this does not select a UPS model.
Example results for load (watts)
These examples use Load power factor: 0.8; Runtime wanted (minutes): 15; Battery-to-load efficiency (%): 90; Capacity reserve (%): 20. They are reference calculations, not recommended settings.
| Load (watts) | Apparent capacity scenario (VA) |
|---|---|
| 300 | 450 |
| 600 | 900 |
| 1200 | 1800 |