How it works
A steady balanced load at the stated voltage and power factor. Starting surges, harmonics, neutral current, branch-circuit rules and protective-device selection are excluded. This calculates load current; it does not certify a circuit or choose a wire size.
Worked example
A 3,000 W load with a power factor of 0.8 on a 240 V single-phase supply has an apparent power of 3,750 VA and draws 15.6 A.
How the load current changes with real power load
Other inputs keep their starting values: Power factor: 0.8; Supply voltage (volts): 240; Supply type (1 = single phase, 3 = balanced three phase): 1. Examples only, not recommendations.
| Real power load (watts) | Load current (amps) |
|---|---|
| 1,500 | 7.8125 |
| 3,000 | 15.625 |
| 6,000 | 31.25 |