How it works
Heating-only balance: (envelope W/K + ventilation W/K) times temperature difference, minus entered gains, bounded at zero. Supply coefficients from an appropriate survey or design calculation; this tool does not derive them from floor area. It excludes transient warm-up, humidity, cooling, duct losses and equipment sizing. It is not ACCA Manual J or a code-compliance calculation. One international-table Btu equals 1055.05585262 joules.
Worked example
A building with an envelope heat-loss coefficient of 250 W/K and a ventilation coefficient of 60 W/K, at a 25 °C indoor-outdoor design difference, has a heating load of 7,750 W, or 26,444 BTU/hr.
How the calculated heating load changes with envelope heat-loss coefficient
Other inputs keep their starting values: Indoor minus outdoor design temperature (C): 25; Ventilation heat-loss coefficient (W / kelvin): 60; Internal and solar heat gains (watts): 0. Examples only, not recommendations.
| Envelope heat-loss coefficient (W / kelvin) | Calculated heating load (BTU/hour) |
|---|---|
| 125 | 15,781.155053 |
| 250 | 26,444.097657 |
| 500 | 47,769.982864 |